STS Fire Protection System | Powder Coating Plant

Seica Logo.png
Gallery

STS provides fire protection systems for powder coating plants, including advanced control systems that ensure safe and efficient operations for both automatic and manual coating processes.

EPS + LSMK Control System Features:

  • Touch Display with event memory

  • UPS with lightning protection (Class 2 + 3)

  • Over/Undervoltage Protection (24V DC)

  • EMV Improvements according to latest standards

  • TÜV Certification for safety compliance

  • PL d Fire Detection System with forwarding & signaling

  • 2-Channel Safety Contacts for fire detection & operational readiness

  • Custom Extensions available for specific needs

  • Remote Access via VPN

  • Data Backup via USB stick

Product Video

Technical Specifications

  • Supply Voltage: 100–500V AC, 50/60Hz

  • Current: 0.8A

  • Fire Protection System Fusing: 6A, permanent voltage supply with separate fuse protection before the main switch

  • Operating Voltage: 24V DC (22 to 27.5V DC)

  • Overvoltage Category: III

  • Protection Type (Control Cabinet): IP54

  • Max. Installation Height: 2000m above NN

  • Response Time (Typical): 330ms (Flame detector FL8 or FL9: UV + IR channel, UV on 50ms)

  • Potential-Free Safety Contacts: Max. 24V DC 5A / 230V AC 3A

  • Temperature Range (Fire Protection System): +10°C to +45°C with max. 95% relative humidity


Technical specifications may vary depending on the selected configuration. Please contact us for detailed specifications tailored to your requirements.